KWN61-40.5 Air insulated metal dadmowable switchgear is an indoor switdhgear,assembly operating under theconditions of50/60Hz three phaseand rated 40.5kV AC voltage,which is applied to the transmission anddistribution for gene ators.transformer substations and the industy and mine enterprises It also can be used to control,protect and monitor electicdircuits,and very usefulfor fiequent operating condition
Standard IEC62271-200
Contact Us
KYN61-40.5 Air insulated metal clad movable switchgear is an indoor switchgear,assembly operating under the conditions of 50/60Hz three phase and rated 40.5kV AC voltage,which is applied to the transmission and distribution for generators,transformer substations and the industry and mine enterprises. It also can be used to control,protect and monitor electric circuits,and very useful for frequent operating conditions.
Standard: IEC62271-200
1.Ambient air temperature: -15℃ ~+40℃
2.Altitude: ≤1000m
3.Relative humidity : Daily average≤95%; Monthly average≤90% 4. Earthquake 4.intensity:≤magnitude 8.
5.Applicable in the places without corrosive and flammable gas.
Note: Customized products are available.
1.The cabinet is made of aluminum-zinc coated sheet processed by CNC equipment and assembled with bolts or rivets, with a fully modular structure.
2.This switchgear has various functions to prevent misoperations, including preventing loaded trolleys from moving, preventing live coupling and earthing switches, and preventing inadvertent entry into live compartments.
3.The switchgear is equipped with a ZN85 vacuum circuit breaker with excellent performance and a handcart, and the main busbar is connected without the need for transitional transfer.
4.This switchgear is an advanced, stable performance, reasonable structure, easy-to-
use, safe and reliable power distribution equipment
No. | Item | Unit | Value | |
1 | Rated voltage | kV | 40.5 | |
2 | Rated current | A | 630/1250/1600/2000/2500 | |
3 | Rated frequency | Hz | 50/60 | |
4 | Power frequency withstand voltage in 1 min | Phase,Earthed | kV | 95 |
lsolating Fracture | kV | 110 | ||
5 | Lightning impulse withstand voltage(Peak) | Phase,Earthed | kV | 185 |
lsolating Fracture | kV | 215 | ||
6 | Rated current of the main busbar | A | 630/1250/1600/2000/2500 | |
7 | Rated current of the branch busbar | A | 630/1250/1600/2000/2500 | |
8 | Rated short-circuit breaking current | kA | 20/25/31.5 | |
9 | Rated short-time withstand current | kA | 20/25/31.5 | |
10 | Rated peak withstand current | kA | 50/63/80 | |
11 | Rated short circuit making current | kA | 50/63/80 | |
12 | Frequency withstand voltage in 1min of aux control loop | V | 2000 | |
13 | lnternal arc duration test(0.5s) | kA | 31.5 | |
14 | Degress of protection | IP | IP4X(IP2X when the front door is opened) | |
15 | Rated voltage of aux control loop | V | AC or DC 110/220 |
ZN85-40.5 parameter
No. | Item | Unit | Data | |||
1 | Rated voltage | kV | 40.5 | |||
2 | Rated insulation level | lightning impulse withstand voltage (full wave) | kV | 185 | ||
1 min power frequency withstand voltage | kV | 95 | ||||
3 | Rated frequency | Hz | 50 | |||
4 | Rated current | kA | 630 | 630/1250 | 1250/1600/2000/2500 | |
5 | Rated short -circuit breaking current | kA | 20 | 25 | 31.5 | |
6 | Rated short -circuit making current | kA | 50 | 63 | 80 | |
7 | Rated withstands current (peak) | kA | 50 | 63 | 80 | |
8 | Rated short-time withstand current | kA | 20 | 25 | 31.5 | |
9 | Fixed breaking time | s | ≤0.07 | |||
10 | Making time | Electro-magnetic mechanism | s | Electro-magnetic mechanism≤0.2 | ||
Spring mechanism | s | Spring mechanism ≤0.10 | ||||
11 | Rated operation sequence | / | Open-0.3s-close open-180s-close open | |||
12 | Mechanical life | times | 10000 |